Safety relay module
Safety relay module SRM 21 RT2
Material no.: 1179203 Old material no.: 90560049
Stock type
contact usProduct features
- Enclosure width: 22.5 mm
- 2 NC or 1 NC/1 NO contact can be connected
- Feedback circuit
- 2 enabling paths
- 1 transistor output
- Manual or automatic reset
- LED indicator for switching condition
- Crossed wire monitoring
Technical data
General technical data
Applied standards
EN ISO 13849-1, EN 62061, EN 60204-1, BG-GS-ET-20, EN 60947-5-1, EN 60947-5-3, EN 61326-3-1
Enclosure
polycarbonate, black
Tightening torque
screw connection terminals: approx. 0.8 Nm
Degree of protection
enclosure IP40, terminal block IP20 to IEC/EN 60529, protection against contact to VBG 4
Contact material
Silver, gold flashed
Mounting
DIN rail mounting
Connection
screw connection terminals with + and - screws
Cable cross-section
min. 1x 0.5 mm² (AWG 20) including conductor ferrules, max. 1x 2.5 mm² (AWG 14) including conductor ferrules, 2x 1.5 mm² (AWG 16) including conductor ferrules
Rated operating voltage Ue
24 VDC ±15 %
Rated operating current Ie
0.125 A
Rated insulation voltage Ui
250 VAC
Rated impulse withstand voltage Uimp
4 kV
Conditional short-circuit current
100 A
Inputs
1 NC/1 NO contact or 2 NC contacts, 1 feedback circuit, 1 start input (monitored)
Outputs
2 enabling paths, 1 transistor output as signalling output
Rated operating current/voltage Ie/Ue
to EN 60947-5-1: 2 A/230 VAC; 1 A/24 VDC
to CSA: B300/R300, 250 VAC
Conventional thermal current Ithe
5 A
Utilisation category
AC-15; DC-13
Contact load capacity
min. 10 mA
Typ. input voltage
20 VDC
Typ. input current
22 mA
Max. load of signalling output
20 mA
Short-circuit protection
power supply 2A slow blow, enabling paths 6 A gG/gN fuse
Pick-up delay
≤ 20 ms
Drop-out delay
≤ 20 ms
Risk time
≤ 0.5 s (switch-on delay)
Attendance delay tv
< 200 ms
Mechanical life
> 50 million operations
Display
1 LED for supply voltage, 1 LED each for input A and B, 1 LED for authorisation
Degree of pollution
2
Overvoltage category
III
Ambient temperature
–22 °C … +55 °C
Storage and shipping temperature
–22 °C … +70 °C
Relative humidity
10 % ... 90 %
Shock resistance
15 g
Approvals
ß d
Note
Inductive loads (contactors, relays etc.) are to be suppressed by suitable circuitry.
Weight
220 g
Safety-relevant data
EN ISO 13849-1
Performance Level PL e
Category
4
TM
max. 20 years
MTTFd
> 113 years
DC/DCavg
> 99 %
EN 62061
SIL CL 3
PFHd
3 x 10-8 1/h
hop
8 h/day
dop
220 days/year
tzyklus
30 s
EN 60204-1
stop category 0
Note
The safety-related data are based on a load of 24 V / 1 A / DC-1 for the enabling paths. With higher load currents for the enabling paths and other requirement rates nop, the safety-related data vary from the given data and can be provided on request.