Ex magnetic sensor

Ex RC 13,5


  • Ex zone 1 and 21

  • Brass enclosure, nickeled

  • Actuation from front

  • Switching distance up to 30 mm depending on the actuating magnet

  • With pre-wired cable

  • Attention: Please state required international approvals with your order!

Notes
  • 2 mounting nuts are included in delivery

  • The actuator is not included in the delivery of the switches

Technical data

Applied standards

EN IEC 60947-5-2, EN IEC 60079-0, EN 60079-18

Enclosure

brass, nickeled

Degree of protection

IP67 (IEC/EN 60529)

Actuating magnet

series M permanent magnet

Switching system

reed contacts

Switching elements

NC contact, NO contact or
change-over contact

Connection

pre-wired cable H05VV-F or Ölflex Heat 125 (depending on the variant)

Cable cross-section

1S, 1Ö: 3 x 0.75 mm²
1W: 4 x 0.75 mm²

Cable length

2, 5 or 10 m

Switching voltage

max. 250 VAC/DC

Switching current

1Ö, 1W: max. 0.5 A DC / max. 0.35 A AC,
1S: max. 1.5 A

Short-circuit current Ik

1Ö, 1W: max. 2 A, 1S: max. 5 A

Switching capacity

1Ö, 1W: max. 30 W/VA, 1S: max. 100 W/VA

Bounce duration

1Ö, 1W: max. 4.5 ms, 1S: max. 5 ms

Ambient temperature

–20 °C … +70 °C,
on request: –40 °C … +70 °C

Mechanical life

> 1 million operations

Vibration resistance

1Ö, 1W: max. 15 g, 1S: max. 30 g

Impact energy

max. 7 J

Ex marking

L II 2G Ex mb IIC T6 Gb,
L II 2D Ex mb IIIC T80 °C Db
IECEx Ex mb IIC T6 Gb
Ex mb IIIC T80 °C Db

Approvals

DMT 01 ATEX E 058 X
IECEx BVS 07.0007 X
f a
< on request
Ü on request

Downloads

Loading...
Mounting and wiring instructions – Ex RC

German, English, French, Italian, Portuguese

PDF 944 KB 28.09.2023
Please go to the relevant product pages for additional downloads.

Variants / Options

The following variants / options are available on request:

  • Cold-resistant version down to -40 °C

  • Special version only for gas Ex zone 2 and dust Ex zone 22

  • Maritime certification to DNV <

to your contact persons