Technical data
General technical data
Applied standards
EN 60947-5-1, EN ISO 13849-1, emergency stop devices: EN 60947-5-5 and EN ISO 13850
Enclosure
thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0
Degree of protection
IP65/IP67 (IEC/EN 60529)
B10d (10 % load)
60 000
TM
max. 20 years
Contact material
silver
Switching system
slow action, positive break NC contacts A
Switching elements
1 NC/1 NO contact or 2 NC contacts, type Zb
Connection
pre-wired cable H05VV-F
Cable cross-section
4 x 0.75 mm²
Cable length
1 m
Rated impulse withstand voltage Uimp
4 kV
Rated insulation voltage Ui
250 V
Conventional thermal current Ithe
6 A
Rated operating current/voltage Ie/Ue
6 A/250 VAC; 0.25 A/230 VDC
Utilisation category
AC-15; DC-13
Short-circuit protection
6 A gG/gN fuse
Ambient temperature
–20 °C … +75 °C
Mechanical life
> 30 000 operations
Operation cycles
max. 1800/h
Contact opening
max. 2 x 4 mm
Approvals
a
Downloads
Variants / Options
The following variants / options are available on request:
Contact overlapping
Other cable lengths
Gold-plated contacts
Plug-in connector M12 x 1, 4-pole
Cable entry on side