Command device

ES 14 QRUV 2Ö 2m -40°C...+65°C Extreme

Article no.: 1264315

contact us

Product features

  • Cold-resistant down to -40 °C

  • Thermoplastic enclosure

  • Double insulated X

  • Mounting hole diameter 22.5 mm

  • Mounting details to EN 50047

  • With pre-wired cable

  • Actuator: Emergency-stop push button QRUV

  • Actuator made of plastic

  • Projection from front of panel 41 mm

  • Reset by turning right or left

  • Attention: Please state required international approvals with your order!

Technical data

Applied standards

EN 60947-5-1, EN 60947-5-5, EN ISO 13849-1, EN ISO 13850

Enclosure

thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0

Degree of protection

IP67 to IEC/EN 60529, use only with enclosure for command devices

B10d (10 % load)

60 000

TM

max. 20 years

Contact material

silver

Switching system

slow action, positive break NC contacts A

Switching elements

2 NC contacts, type Zb

Connection

cable 4 x AWG 20

Cable cross-section

4 x 0.56 mm²

Cable length

2 m

Rated impulse withstand voltage Uimp

4 kV

Rated insulation voltage Ui

250 V

Conventional thermal current Ithe

6 A

Rated operating current/voltage Ie/Ue

6 A/250 VAC; 0.25 A/230 VDC

Utilisation category

AC-15; DC-13

Short-circuit protection

6 A gG/gN fuse

Ambient temperature

–40 °C … +65 °C

Mechanical life

> 30 000 operations

Operation cycles

max. 1800/h

Contact opening

max. 2 x 4 mm

Approvals

d

Weight

154 g

Downloads

Loading...
Mounting and wiring instructions – ES 14 Extreme

German, English, French, Italian, Portuguese, Russian

PDF 2 MB 21.09.2023

Variants / Options

The following variants / options are available on request:

  • Cable entry on side
to your contact persons

Other interesting products

Alternative version with explosion protection

Ex

Command device

ES 14 QRUV 2Ö 2m -40°C...+65°C Extreme

Article no.: 1264315

contact us